The beginnings of our team go back in the past when people were already involved in same or similar projects and fields of working.
Our team of people has vast experiences in the branch building turnkey or partial solutions.
With this knowledge, we can provide the best services in the field of Engineering, Installation, and Maintenance.
Some of the projects, where our team was involved are:
Chemical industry, Central Laboratory (2022)
Year of execution: 2022
Area: Cooling
Equipment used: 1 pc Liebert HPM SOFKA+HCR 14
Short project description:
We have provided DX cooling system (Air-cooled, direct expansion version fitted with a scroll compressor) for the Central Laboratory room.
The required range of temperature/humidity in the room is:
- The internal temperature: + 23 ±0,3ºC
- Relative humidity: 50% RH ± 2%;
Total built-in net sensible cooling capacity is 6 kW
Szamhead Kft (2015-2022)
Year of execution: 2015-2022
Area: UPS
Equipment used: 6 pcs Liebert APM (150kW)
Short project description:
Delivery, installation and start-up of modular UPS devices Liebert APM (6 pcs) with 150kW of total power each and with batteries for 10-15 min autonomy. Our company is in charge of regular maintenance and readiness service of these devices.
Total installed power is 900kW or 0,90 MW.
World leading networking company (2022)
Year of execution: 2022
Area: Cooling
Type of units used in the project:
- 1 pcs Liebert PDX 033+HCR 43
Short project description:
We have provided DX cooling system (Air-cooled, direct expansion version, fitted with a scroll compressor) for the server room.
The required range of temperature/humidity in the room was:
- The internal temperature: + 24 ± 0,5ºC
- Relative humidity: 45% RH ± 5%;
The total built-in net sensible cooling capacity is 30 kW.
Public Administration Server Room (2022)
Year of execution: 2022
Area: rack PDU Power Distribution Unit
Equipment used:
- 100+ units Vertiv Geist intelligent rack PDU strip
Short project description:
In the server room, special requirements for the intelligent distribution strips were the socket type and quantity per section field and per phase, wide input voltage range and the possibility to integrate into building management system.
METRO stores (2016-2022)
Year of execution: 2016-2022
Area: Cooling
Equipment used:
- Server room: 8 pcs Liebert HPM S1GUA+HCR 24,
Short project description:
We have provided DX cooling system for the server room. We have installed 78pieces Liebert CRAC air-cooled, DX units fitted with a scroll compressor.
The required range of temperature/humidity in the rooms is:
- The internal temperature: + 24 ± 1,0ºC
- Relative humidity: 50% RH ± 5%
Total built-in net sensible cooling capacity is 144 kW.
Telecommunication company (2022)
Year of execution: 2022
Area: UPS
Equipment used:
- 1 unit Liebert APM (90kW) modular UPS
Short project description:
With this APM UPS device, the APM modular UPS installed base under the maintenance and readiness service of Prom-Tech Hungary Kft. increased up to 3,3 MW.
Automotive electrical systems factory (2022)
Year of execution: 2022
Area: Cooling
Type of units used in the project:
- 2 pcs Liebert HPSE+HPSC 06
Short project description:
We have provided a cooling system for two individual Switch rooms with DX split precision Liebert Cooling units.
The required range of temperature/humidity in the rooms was:
- The internal temperature: + 30 ± 1ºC
- Relative humidity: 35% RH ± 5%
The total built-in net sensible cooling capacity is 20 kW.
Public Sector (2022)
Year of execution: 2022
Area: rack PDU Power Distribution Unit
Equipment used:
- 160 units Vertiv Geist intelligent rack PDU strip
Short project description:
There was a need for a special, 0U format, intelligent distribution strip inside the racks for a new server room environment. We delivered compact, measurable PDUs with splash-proof connector to meet customer requirements.
Telecommunication company (2022)
Year of execution: 2022
Area: Cooling
Equipment used:
- 1 pc VERTIV PDX PX 047DF+1xDYS035
Short project description:
We have provided DX cooling system (Air-cooled, direct expansion version, fitted with a scroll compressor) for the server room.
The required range of temperature/humidity in the rooms was:
- The internal temperature: + 24 ± 0,5ºC
- Relative humidity: 50% RH ± 5%
The total built-in net sensible cooling capacity is 40 kW.
Electric Utility company (2022)
Year of execution: 2022
Area: UPS
Equipment used:
- Vertiv Liebert GXT5
Short project description:
The customer wanted to protect the costly and sensitive IT equipment they have, considering utilizing a generator on-site when utility power fails for a longer period.
We managed to implement a UPS solution that is highly available and flexible enough and has a unity power factor and high energy efficiency.
Banking and insurance sector (2021)
Year of execution: 2021
Area: rack PDU Power Distribution Unit
Equipment used:
- 150+ units Vertiv Geist intelligent rack PDU strip
Short project description:
A financial services institution was seeking a solution for IT rack power distribution with intelligent management in their data center. We provided a solution with PDU devices featuring outlet level switching & outlet level monitoring at the same time. Each of the types supplied belongs to the best in the class category of PDU technology.
Telecommunications Budapest (2021)
Year of execution: 2021
Area: Cooling
Type of units used in the project:
- 1 pc Liebert PCW PH145DC
Short project description:
We have provided a cooling system for the server room in three phases with a total of 5 pieces of Liebert CRAC chilled water precision units.
The required range of temperature/humidity in the rooms was:
- The internal temperature: + 24 ± 1,0ºC
- Relative humidity: 50% RH ± 5%
- Inlet fluid temperature: 7ºC
- Outlet fluid temperature: 12ºC
The total built-in net sensible cooling capacity is 145 kW.
Electronics industry server room (2021)
Year of execution: 2021
Area: Cooling
Type of units used in the project:
- 1 pc VERTIV PDX PX 074DA+2xHCR 43
Short project description:
We have provided and installed a DX cooling system for the Server room (air-cooled, direct expansion Liebert CRAC unit fitted with a scroll compressor).
The required range of temperature/humidity in the rooms was:
- The internal temperature: + 24 ± 1,0ºC
- Relative humidity: 50% RH ± 5%
The total built-in net sensible cooling capacity is 30 kW.
IT service industry server room (2021)
Year of execution: 2021
Area: Cooling
Type of units used in the project:
- 1 pc Liebert PDX PX 33 DA+HCR 43
Short project description:
We have provided and installed a DX cooling system for the Server room (air-cooled, direct expansion Liebert CRAC unit fitted with a scroll compressor).
The required range of temperature/humidity in the room was:
- The internal temperature: + 24 ± 1,0ºC
- Relative humidity: 50% RH ± 5%
The total built-in net sensible cooling capacity is 30 kW.
Chemical industry laboratory (2021)
Year of execution: 2021
Area: Cooling
Equipment used:
Type of units used in the project:
- 1 pc Liebert HPM S1EOA+HCR 17
Short project description:
We have provided and installed a DX cooling system for the Laboratory (air-cooled, direct expansion Liebert CRAC unit fitted with a scroll compressor).
The required range of temperature/humidity in the room was:
- The internal temperature: + 20 ± 2,0ºC
- Relative humidity: 65% RH ± 4%; 50% RH ± 4%
The total built-in net sensible cooling capacity is 14 kW.
Military base (2021)
Year of execution: 2021
Area: Cooling
Type of units used in the project:
- 4 pcs Liebert HPSE+HPSC 10
- 2 pcs Liebert HPSE+HPSC 140
Short project description:
We have provided a cooling system for two individual Switch rooms in two buildings with a total of 6 pieces DX split precision Liebert Cooling units.
The required range of temperature/humidity in the rooms was:
- The internal temperature: + 24 ± 1,0ºC
- Relative humidity: 50% RH ± 5%
The total built-in net sensible cooling capacity is 70 kW.
National energy supply (2020)
Year of execution: 2020
Area: Cooling
Type of units used in the project:
- 8 pcs Liebert HPW WM15MD
- 2 pcs Liebert HPW WM08MD
Short project description:
We have provided a cooling system for three individual Switch rooms in two buildings with a total of 10 pieces DX compact precision Liebert HPW Outdoor Package Cooling units.
The required range of temperature/humidity in the rooms was:
- The internal temperature: + 24 ± 1,0ºC
- Relative humidity: 50% RH ± 5%
The total built-in net sensible cooling capacity is 136 kW.
Building industry testing laboratory (2020)
Year of execution: 2020
Area: Cooling
Type of units used in the project:
- 2 pcs Liebert HPM S1DOA+HCR 17
Short project description:
We have provided and installed a DX cooling system for the Laboratory (air-cooled, direct expansion Liebert CRAC unit fitted with a scroll compressor).s.
The required range of temperature/humidity in the rooms was:
- The internal temperature: + 20 ± 2,0ºC
- Relative humidity: 65% RH ± 4%; 50% RH ± 4%
The total built-in net sensible cooling capacity is 20 kW.
Chemical industry central laboratory (2020)
Year of execution: 2020
Area: Cooling
Type of units used in the project:
- 2 pcs Liebert HPM S0HOA+HCR 14
Short project description:
We have provided and installed a DX cooling system for the Laboratory (air-cooled, direct expansion Liebert CRAC unit fitted with a scroll compressor).
The required range of temperature/humidity in the rooms was:
- The internal temperature: + 20 ± 2,0ºC
- Relative humidity: 65% RH ± 4%; 50% RH ± 4%
The total built-in net sensible cooling capacity is 14 kW.
Textile industry testing laboratory (2020)
Year of execution: 2020
Area: Cooling
Type of units used in the project:
- Server room: 2 pcs Liebert HPM S0HOA+HCR 14
Short project description:
We have provided and installed a DX cooling system for the Laboratory (air-cooled, direct expansion Liebert CRAC unit fitted with a scroll compressor).
The required range of temperature/humidity in the rooms was:
- The internal temperature: + 20 ± 2,0ºC
- Relative humidity: 65% RH ± 4%; 50% RH ± 4%
The total built-in net sensible cooling capacity is 14 kW.
Magyar Telekom Budapest (2019)
Year of execution: 2019
Area: Cooling
Equipment used:
- 4pcs Liebert PCW PH095DC
Short project description:
We have provided a cooling system for a Data Center with a total of 4 pieces of chilled water precision Liebert CRAC units. Our task was also the removal of the old units.
The required range of temperature/humidity in the rooms was:
- The internal temperature: + 22 ± 1,0ºC
- Relative humidity: 50% RH ± 5%
- Inlet fluid temperature: 7ºC
- Outlet fluid temperature: 12ºC
The total built-in net sensible cooling capacity is 400 kW.
Public institution (2019)
Year of execution: 2019
Area: Cooling
Equipment used:
- 1pcs Liebert PCW PH080DC
- 1pcs Liebert HPM S29OC
Short project description:
We have provided a cooling system for the server room with a total of 2 pieces Liebert chilled water precision CRAC units.
The required range of temperature/humidity in the rooms was:
- The internal temperature: + 24 ± 1,0ºC
- Relative humidity: 50% RH ± 5%
- Inlet fluid temperature: 9ºC
- Outlet fluid temperature: 14ºC
The total built-in net sensible cooling capacity is 130 kW.
DENINET (2019)
Year of execution: 2019
Area: Cooling
Equipment used:
- 2pcs Liebert HPM S29UC
Short project description:
We have provided a chilled water precision cooling system for the server room.
The required range of temperature/humidity in the rooms were:
- The internal temperature: + 24 ± 1,0ºC
- Relative humidity: 50% RH ± 5%
- Inlet fluid temperature: 7ºC
- Outlet fluid temperature: 12ºC
Total built-in net sensible cooling capacity is 60 kW.
Hotel Budapest (2019)
Year of execution: 2019
Area: Cooling
Equipment used:
- 2 pcs Liebert HPM S1DOA+HCR 17
Short project description:
We have provided DX cooling system for the server room. We have installed 2 pieces of Liebert CRAC direct expansion units, fitted with a scroll compressor.
The required range of temperature/humidity in the rooms were:
- The internal temperature: + 24 ± 1,0ºC
- Relative humidity: 50% RH ± 5%
Total built-in net sensible cooling capacity is 40 kW.
Vodafone Hungary (2018-2019)
Year of execution: 2018-2019
Area: UPS
Equipment used:
- 1pcs Liebert APM (120kW)
Short project description:
Delivery, installation, and start-up of modular UPS device Liebert APM (120kW) together with the installation of batteries with back –up time up to 15min.
Office building in Budapest (2018-2019)
Year of execution: 2018-2019
Area: UPS
Equipment used:
- 2pcs Liebert EXL (400kW)
- 4pcs Liebert EXL (200kW)
- 2pcs Liebert EXL (100kW)
- 1pcs Liebert NXC (30kW)
Short project description:
Delivery, installation, and start-up of all UPS devices together with the installation of batteries with back –up time up to 30min.
Total installed power is more than 1,8 MW.
Graphisoft Park Budapest (2018)
Year of execution: 2018
Area: Cooling
Equipment used: 3 pcs VERTIV Liebert CRV21RA+HCR 33
Short project description:
We have provided DX cooling system for the server room. We have installed Liebert In the Row CRAC air-cooled, DX units fitted with a scroll compressor.
The required range of temperature/humidity in the room is:
- The internal temperature: + 37 ± 1,0ºC
- Relative humidity: 24% RH ± 5%
Total built-in net sensible cooling capacity is 60 kW.
TEVA (2018)
Year of execution: 2018
Area: UPS
Equipment used: 1pcs Liebert NXC (60kW)
Short project description:
Delivery, installation and start-up of UPS device together with the installation of batteries with back –up time up to 10min.
Our company is also in charge of regular maintenance and readiness service on this location.
International investment bank (2017-2018)
Year of execution: 2017-2018
Area: UPS
Equipment used:
- 2pcs Liebert APM (120kW)
- 2pcs Liebert NXC (15kW)
- 2pcs Chloride Cross Rack (160A)
Short project description:
Delivery, installation, and start-up of modular UPS devices Liebert APM (2pcs) with 120kW of total power each and with batteries for 15min autonomy. We have connected both devices to the system over STS switches.
Delivery, installation, and start-up of UPS devices Liebert NXC (2pcs) with 15kW of total power each and with batteries for 15min autonomy.
We also made a setup of LIFE services on all of the devices. Some of them are connected to LIFE over simple analog lines, some of them are using IP.
Our company is also in charge of regular maintenance and readiness service of these devices for the period of the next 5 years.
Total installed power is 270kW.
Nidec Sole Motor Bercel (2018)
Year of execution: 2018
Area: Cooling
Equipment used:
- 2 pcs VERTIV Liebert PDX PX 031UA+HCR 43
- 1 pcs VERTIV Liebert HPM S0FA+HCR 14
Short project description:
We have provided DX cooling system for the server room and hall. We have installed Liebert CRAC air-cooled, DX units fitted with a scroll compressor.
The required range of temperature/humidity in the room is:
- The internal temperature: + 21 ± 1,0ºC
- Relative humidity: 50% RH ± 5%
Total built-in net sensible cooling capacity is 56 kW.
TechMahindra (2016-2018)
Year of execution: 2016-2018
Area: UPS
Equipment used:
- 1 pcs Liebert APM (30+30kW)
- 3pcs Liebert APS (10kW (2pcs), 20kW)
Short project description:
Delivery, installation, and start-up of modular UPS devices Liebert APM (1pcs) with 30+30kW and Liebert APS (3pcs). All the devices have installed batteries with back-up time up to 60min.
Our company is also in charge of regular maintenance and readiness service of these devices.
MILL Park Budapest (2018)
Year of execution: 2018
Area: Cooling
Equipment used: 2 pcs VERTIV Liebert PDX PX 054DA+HBR 88
Short project description:
We have provided DX cooling system for the server room. We have installed Liebert CRAC air-cooled, DX units fitted with a scroll compressor.
The required range of temperature/humidity in the room is:
- The internal temperature: + 26 ± 1,0ºC
- Relative humidity: 40% RH ± 5%
Total built-in net sensible cooling capacity is 100 kW.
CTBTO server Budapest (2018)
Year of execution: 2018
Area: Cooling
Equipment used:
- 1 pcs VERTIV Liebert PDX PX 031DD+HCR 51
Short project description:
We have provided DX cooling system for the server room. We have installed Liebert CRAC air-cooled, DX unit fitted with a scroll compressor.
The required range of temperature/humidity in the room is:
- The internal temperature: + 24 ± 1,0ºC
- Relative humidity: 50% RH ± 5%
Total built-in net sensible cooling capacity is 21 kW.
Courthouse Hódmezővásárhely (2017)
Year of execution: 2017
Area: Cooling
Equipment used:
- 1 pcs Liebert HPM S0HUA+HCR 17
Short project description:
We have provided DX cooling system for the server room. We have installed Liebert CRAC air-cooled, DX unit fitted with a scroll compressor.
The required range of temperature/humidity in the room is::
- The internal temperature: + 24 ± 1,0ºC
- Relative humidity: 50% RH ± 5%
Total built-in net sensible cooling capacity is 10kW.
Football Stadium Székesfehérvár (2017)
Year of execution: 2017
Area: Cooling
Equipment used:
- 2 pcs Liebert PDX PX 33 DA+HCR 43
Short project description:
We have provided DX cooling system for the server room. We have installed 3 pieces Liebert CRAC air-cooled, DX units fitted with a scroll compressor.
The required range of temperature/humidity in the room is::
- The internal temperature: + 24 ± 1,0ºC
- Relative humidity: 50% RH ± 5%
Total built-in net sensible cooling capacity is 60 kW.
HIPO Budapest (2017)
Year of execution: 2017
Area: Cooling
Equipment used:
- 3 pcs Liebert HPM S1GDA+HCR 33
Short project description:
We have provided DX cooling system for server room. We have installed 3 pieces Liebert CRAC air-cooled, DX units fitted with a scroll compressor.
The required range of temperature/humidity in the room is:
- The internal temperature: + 24 ± 1,0ºC
- Relative humidity: 50% RH ± 5%
Total built-in net sensible cooling capacity is 47 kW.
APOLLO Tyres Hungary Gyöngyös (2016-2017)
Year of execution: 2016-2017
Area: Cooling
Equipment used:
- MRS building: 4 pcs Liebert HPW WM15MD
- PRS building: 4 pcs Liebert HPW WM15MD
Short project description:
We have provided a cooling system for two individual Switch rooms in two buildings with a total of 8 pieces DX compact precision Liebert HPW Outdoor Package Cooling units.
The required range of temperature/humidity in the rooms was:
- The internal temperature: + 24 ± 1,0ºC
- Relative humidity: 50% RH ± 5%
Total built-in net sensible cooling capacity is 120 kW.
National Instruments (Debrecen) calibration rooms (2016)
Year of execution: 2016
Area: Cooling
Equipment used:
- Liebert PDX PX021 + HCR 43 (4pcs)
Short project description:
Two calibration laboratories used for calibration of sensors, instruments were provided with cooling system in 2N redundancy.
The required range of temperature/humidity in this calibration rooms are:
- The internal temperature : + 23°C ± 1,0ºC
- Relative humidity : 45% RH ± 5%
The required range must be provided in six different measurement points in the room at the same time.
International investment bank (Budapest, 2016)
Year of execution: 2016
Area: UPS
Equipment used:
- 2pcs Liebert APM (120kW)
Short project description:
Delivery, installation and start-up of modular UPS devices Liebert APM (2pcs) with 120kW of total power each and with batteries for 15min authonomy. We also made a setup of LIFE services for both devices.
Our company is in charge for regular maintenance and readiness service of this devices for the period of next 5 years.
Hamburger Hungaria (Dunaújváros) power plant (2015)
Year of execution: 2015
Area: UPS
Equipment used:
- Central building: 2pcs Liebert PCW PH025HC
- Electrical building: 4pcs Liebert PCW PH025HC, 4pcs Liebert PCW PH080HC
- Turbine hall: 1pc Liebert PCW PH100HC
Short project desription:
We have provided cooling system for six individual rooms in three buildings with a total of 11 pieces of chilled water precision Liebert CRAC units.
The required range of temperature/humidity in the rooms were:
- The internal temperature: + 24 ± 1,0ºC
- Relative humidity: 50% RH ± 5%
- Inlet fluid temperature: 10ºC
- Outlet fluid temperature: 15ºC
Total built-in net sensible cooling capacity is 410 kW.
Company dealing with mutual funds
Construction of a Highly Secure Room with 35m2 net space with complete support infrastructure in the following configuration: Uninterruptible Power Supply System (UPS) 60kW, Air Conditioning (2x35kW), Electrical installations with Switching blocks, Server and Communication Racks, Fire Extinguishing System with NOVEC1230 gas, Intelligent PDU’s, Designing.
Electrical institute
Super computer data center for hydrodynamic calculation. Scope of supply was: 1 x NXa 160, 1 x NXa 40, 6 x Cool therm 30kW, 1 x HPM 80kW, 1 x 250kW Chiller
Pharmaceutical company
Construction of a Highly Secure Room with 30m2 net space with complete support infrastructure in the following configuration: Uninterruptible Power Supply System (UPS) 60kW, Air Conditioning (2x35kW), Electrical installations with Switching blocks, Server and Communication Racks, Fire Extinguishing System with NOVEC1230 gas, Intelligent PDU’s, Central Surveillance System, Designing.